Aqualogix Cooling Water Systems

Cooling tower water management

Cut cooling tower water use 15–16%. Validated twice by NREL and GSA.

Both Aqualogix technologies were measured in the field for GSA's Green Proving Ground program. Both findings carry the same deployment recommendation: consider for all cooling towers. Every system supplements your existing chemical treatment.

Aqualogix groundwater treatment and reverse osmosis system installed in a central plant
15–16%less cooling tower makeup water
52–53%less blowdown from each technology on its own: partial softening 52%, blowdown recovery 53%
~90%blowdown reduction with BDRS, partial softening and blowdown recovery combined
2.6–2.8 yrsimple payback at GSA-average conditions

Measured by NREL for the GSA Green Proving Ground program, GPG-045 (2020) and GPG-052 (2023). Combined BDRS figure from the NREL blowdown recovery report, Appendix A. Results are site-specific.

Technology

Four technologies, one controller, configured to your water.

We use these four technologies to configure a system that optimizes for your makeup water chemistry, cooling load and utility rates.

Partial softening skid with duplex softener tanks and controller

Partial Softening

Smart softeners remove hardness from a controlled share of the makeup water. With less scale-forming calcium entering the tower, it can safely run at higher cycles of concentration.

Blowdown reduction
52% (NREL)
Cycles of concentration
2.8 → 4.2
Aqualogix BDR5 blowdown recovery skid with reverse osmosis vessels

Blowdown Recovery

Filtration and low-pressure reverse osmosis purify tower blowdown and return it as zero-hardness makeup. Water that used to go to the sewer goes back to work.

Blowdown reduction
53% (NREL)
Effective cycles
2.8 → 4.9
Aqualogix sidestream filter vessels with controller

Sidestream Filtration

Self-backwashing media filters remove suspended solids down to 3–5 microns from a slipstream of tower water. Cleaner condenser tubes transfer heat better, so the chiller uses less energy.

Filtration
3–5 µm, auto-backwash
Selection basis
DOE FEMP criteria
Aqualogix Controller enclosure with touchscreen HMI

Adaptive Control

Instead of holding a fixed conductivity setpoint, the Aqualogix Controller measures makeup and tower chemistry continuously, calculates the highest safe cycles against every scaling limit, and adjusts as conditions change.

Platform
Industrial PLC + HMI
Integration
BACnet/IP · Modbus TCP
Aqualogix controller touchscreen showing the system overview with towers, water sources and treatment train

Designed to work together

The controller coordinates every technology from one point and logs makeup, blowdown and recovered water continuously. That record supports measurement and verification for performance contracts, and it shows your team exactly what the system is saving.

Custom projects

Engineered systems for central plants and alternative water.

Beyond our packaged skids, we design custom systems for large central plants: groundwater reuse, high-salinity makeup, demineralization and large-scale softening.

Reverse osmosis trains and Aqualogix controller treating groundwater for cooling tower makeup
Groundwater reverse osmosis
Bank of large Aqualogix media filter vessels
Central plant filter bank
Multi-vessel utility water softener with automated valves
Utility plant softener

Federal office complex

Groundwater reuse for cooling tower makeup

Groundwater the building was already pumping to drain is now filtered, softened and treated by reverse osmosis, and is blended with city water (if required) as makeup for the central plant.

Design goal: ~26 million gal/yr of potable water offset

Manufacturing plant · Mexico

Nanofiltration and multi-source blending

A nanofiltration system designed to take rainwater, well water and supplemental sources and blend them into water that is within the plant's specifications for manufacturing.

Finished water: < 250 µS/cm

Other custom work

  • Well and city water blending
  • Central chiller plant makeup systems
  • 900 gpm utility plant softener
  • Utility plant filtration
  • AHU condensate recovery
  • Domestic water filtration
  • High-purity process water

Independent validation

Evaluated twice by NREL for the GSA Green Proving Ground.

The National Renewable Energy Laboratory measured both core Aqualogix technologies in service at a 1,150-ton federal facility. Both evaluations concluded with the same deployment recommendation: consider for all cooling towers.

MeasuredGPG-045GPG-052
TechnologyPartial softeningBlowdown recovery
Makeup water savings15%16%
Blowdown reduction52%53%
Payback (GSA avg.)2.6 yr2.8 yr
Chemical programunchangedunchanged

NREL reports TP-7A40-76756 and TP-2C00-86615. GSA-average conditions are the program's standard basis of 3 million ton-hours per year and $16.76/kgal combined water and sewer.

Savings estimate

Screen your site in a minute.

Enter eight values you probably already know. The example shows a representative 3,000-ton facility; replace it with your own numbers.

Your site

Built-in assumptions: partial softening of 48% of makeup; blowdown recovery of 55% of blowdown; chiller 0.65 kW/ton; FEMP fouling factor 0.10 → 0.03; condenser water limits of 4,000 µS/cm and 800 ppm hardness.

Estimated annual savings

$61,791per year in water, sewer and energy, net of operating costs
Partial softening$24,079
Blowdown recovery$14,766
Sidestream filtration (energy)$22,946
Makeup water reduction21.2%
Blowdown reduction80.8%
Cycles after partial softening7.0
Effective cycles with recovery15.6
Chiller kWh saved per year273,938

Strong candidate — all five screening criteria met

A screening estimate using typical values, not a quotation. An engineered estimate uses your measured water chemistry, chiller data and utility bills.

Request an engineered estimate

Next step

Request an engineered estimate.

Tell us about your facility and we will prepare an engineered estimate for your site, at no cost or obligation. Your savings screen inputs and results are sent with this form.

We will come back with installed cost and savings, equipment selection and sizing, typical installation requirements, and a flow schematic and layout.

Along with the site information sheet, it helps to have these ready:

  • 12 months of water chemistry reports
  • 12 months of chiller kW trend data, if available
  • Recent water and electric bills

Prefer to talk? Call (800) 268-4459 or email info@aqualogix.com.

Site information sheet Fields marked * are required

Facility

Chillers and cooling towers

Is the system a single loop or split into separate loops?

Cooling tower water chemistry

Which of these can you provide?

Plant operation

Do you operate a chiller in the winter?
Do you set back the condenser water temperature at night?
Any problems with tower makeup control?

* Required. We use your details only to respond to this request.

About Aqualogix

A U.S. manufacturer of cooling tower water-savings systems.

Aqualogix LLC designs, builds, commissions and supports its systems both in the United States and internationally. We serve federal, institutional, commercial, data center and industrial central plants.

Headquarters
Palm Beach Gardens, Florida
Systems
Packaged skids from 75 to 3,000 tons; custom central-plant systems beyond
Validation
Two GSA Green Proving Ground evaluations by NREL
GSA MAS
GSA Multiple Award Schedule
Contract 47QSWA23D007G

Contact

Talk with our engineering team.

A short conversation is usually enough to know whether your site is a good fit. If it is, we will prepare an engineered estimate with equipment selection, installed cost and projected savings.

Phone(800) 268-4459
Emailinfo@aqualogix.com
Office4440 PGA Boulevard, Suite 600
Palm Beach Gardens, FL 33410